* Product Overview
A heat pump system that recovers heat from waste water and supplys the recovered heat to the production of cold/hot water and cooling/heating system
* Features
① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems
* Application
Applicable to any sector that generates waste water and requires hot water such as Sauna, Golf club, Eel farm, Dyeing factory
* Specifications of Waste Water Source Heat Pump (IWK-12C Series)
Model |
IWK-12C-60 |
IWK-12C-74 |
||
Capacity |
KW |
209.65 |
260.47 |
|
Kcal/h |
180,300 |
224,000 |
||
USRT |
59.62 |
74.07 |
||
Power Consumption |
KW |
53 |
64 |
|
Power Supply |
3P * 380V * 60Hz |
|||
Compressor Capacity |
HP |
50 |
60 |
|
Dimension |
Length |
mm |
1,450 |
|
Height |
1,750 |
|||
Depth |
1,000 |
|||
Compressor |
Type |
Scroll type |
||
Quantity |
1 |
|||
Operation Method |
Y- |
|||
Volume Control |
% |
0~100% |
||
Refrigeration Ton |
RT |
17.35 |
19.38 |
|
Refrigerant |
Type |
R-407C |
||
Control Method |
Thermostatic expansion valve |
|||
Heat Exchanger at Load-side |
Type |
Brazed Plate type |
||
Circulation Volume |
LPM |
111.3 |
138.27 |
|
Piping(IN/OUT) |
A |
50 |
||
Heat Exchanger at Heat source-side |
Type |
Spiral Tube Type |
||
Piping(IN/OUT) |
A |
150 |
||
Control |
Temperature Control |
Automatic inlet/outlet temperature control |
||
Operation Control |
PCB |
|||
Weight |
kg |
980 |
1,030 |
|
Operational Condition |
Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 70°C; waste water temp to be 20°C; |
■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.