LOGO

IL-JIN E-PLUS

Energy saving device manufacturer, Waste water heat heat pump, Air heat heat pump, Geothermal heat pump and more
Name

Waste Water Source Heat Pump

Model IWM-12B Series
Series Products
Product Description

* Product Overview

A heat pump system that recovers heat from waste water and supplys the recovered heat to the production of cold/hot water and cooling/heating system

 

* Features

① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems

 

* Application

Applicable to any sector that generates waste water and requires hot water such as Sauna, Golf club, Eel farm, Dyeing factory


 

* Specifications of Waste Water Source Heat Pump (IWB-12B series)

Model

IWM-12B-34

IWM-12B-38

IWM-12B-51

IWM-12B-67

Capacity

KW

117.79

133.6

180.47

235.7

Kcal/h

101,300

114,900

155,200

202,700

USRT

33.5

38

51.32

67.03

Power Consumption

KW

32

38

50

58

Power Supply

3P * 380V * 60Hz

Compressor Capacity

HP

30

36

48

56

Dimension

Length

mm

1,200

Height

1,940

Depth

760

Compressor

Type

Scroll type

Quantity

2

4

Operation Method

Direct-on-line

Volume Control

%

0~100%

Refrigeration Ton

RT

10.7

12.36

16.48

19.68

Refrigerant

Type

R-22

Control Method

Thermostatic expansion valve

Heat Exchanger at Load-side

Type

Brazed Plate type

Circulation Volume

LPM

52.76

59.84

80.83

105.57

Piping(IN/OUT)

A

40

50

Heat Exchanger

at Heat source -side

Type

Spiral Tube Type

Piping(IN/OUT)

A

125

Control

Temperature Control

Automatic inlet/outlet temperature control

Operation Control

PCB

Weight

kg

450

500

600

680

Operational Condition

Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 60°C; Waste water temp to be 25°C

■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.