LOGO

IL-JIN E-PLUS

Energy saving device manufacturer, Waste water heat heat pump, Air heat heat pump, Geothermal heat pump and more
Name

Sea Water Source Heat Pump

Model IWS-55A/53A/13A Series
Series Products
Product Description

* Product Overview

An eco-friendly heat pump system that recovers sensible heat from the sea water and supply the recovered heat to the heat/cool the water tank, or produce cold/hot water without using any fossil fuel thereby saving energy and reducing greenhouse gas

 

* Features

① Significantly saving energy costs associated with heating and cooling of the water tank at eel farms and aquaculture farms
② Maintaining the optimum temperature by accurate temperature control for the growth of the young and live fishes
③ Extended equipment life and easy maintenance with the titanium dual pipe and spiral tube heat exchanger
④ Fitted with the aerification system to the heat source tank so as to generate air bubbles to remove sludge and optimize the heat transfer of the evaporator
⑤ Ability to recover heat even from the low temperature heat source (up to 5°C)

 

* Application

Applicable to any sector that uses sea water as a heat source and requires hot water and heating/air-conditioning such as Land aquaculture, Mariculture, Offices near the sea shore, Commercial buildings, Motel, Sauna and so on

 

* Specification of Sea Water Source Heat Pump (IWS-55A, 53A, 13A Series)

Model

IWS-55A-42

IWS-55A-55

IWS-55A-62

IWS-53A-39

IWS-53A-51

IWS-53A-76

IWS-13A-21

KITECH

IJS-30SE

IJS-40SE

IJS-50SE

IJS-DW140

IJS-DW180

IJS-DW260

IJS-BW75

Capacity

Heating

KW

147.88

191.72

216.34

137.5

180

265.5

74.5

USRT

42.06

54.52

61.53

39.1

51.19

75.51

21.19

Cooling

KW

147.15

182.3

203.8

111.2

176.5

207.4

 

USRT

41.85

51.84

57.96

31.62

50.2

58.98

 

Heating/cooling

KW

20.0/24.4

26.20/32.80

34.57/42.94

19.68/3237

26.68/32.37

37.37/42.77

21.92

Power Supply

3Phase x 380V x 60Hz

Refrigeration Cycle

Single

Dual

Single

Dual

Single

Dimension

Length

mm

1,950

1,950

2,200

1,950

1,950

2,600

1,950

Height

1,870

1,870

1,870

1,870

1,870

1,870

1,870

Depth

1,900

1,900

1,900

1,000

1,000

1,000

1,000

Compressor

Type

Scroll type

Quantity

2

1

Driving Method

Y-Δ

Volume Control

%

0~100%

Refrigeration Ton

RT

12.56

16.78

21.06

21.06

16.78

12.52

19.38

Refrigerant

Type

R-410A

Control Method

Thermostatic expansion valve

Heat
Exchanger
at
Load-side

Type

Coaxial type

Brazed Plate type

Circulation Volume

LPM

450

500

600

450

500

600

70

Piping(IN/OUT)

A

75

100

75

100

50

Heat
Exchanger

at Heat source-side

Type

Coaxial type

Titanium Tube type

Piping(IN/OUT)

A

 

   

750

600

450

70

Control

Temperature Control

4way proportional control valve

Operation Control

PCB

Weight

kg

1,100

1,300

1,500

900

1,100

1,200

600

Requirements for certified product

heating

Inlet of heat exchanger at load-side to be 15°C; Inlet of heat exchanger at heat source-side to be 15°C

cooling

Inlet of heat exchanger at load-side to be 25°C; Inlet of heat exchanger at heat-source-side to be 25°C

■ Conditions for IWS-13A-21 are water temperature at the inlet of heat exchanger at the heat-source-side to be 15°C; Inlet and outlet of heat exchanger at the load-side to be 45°C and 60°C