Product Description

* Product Overview

A heat pump system that recovers heat from waste water and supplys
the recovered heat to the production of cold/hot water and cooling/heating system

 

* Features

① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems

 

* Application

Applicable to any sector that generates waste water and requires hot water such as Sauna, Golf club, Eel farm, Dyeing factory

 

* Specifications of Waste Water Source Heat Pump (IWB-12BA series)

Model

IWB-12BA-62

IWB-12BA-74

IWB-12BA-100

IWB-12BA-117

Capacity

KW

218.6

260

353.02

413.14

Kcal/h

188,000

223,600

303,600

355,300

USRT

62.17

73.94

100.4

117.49

Power Consumption

KW

56

66

88

104

Power Supply

3P * 380V * 60Hz

Compressor Capacity

HP

64

72

96

112

Dimension

Length

mm

1,700

Height

1,940

Depth

1,000

Compressor

Type

Scroll type

Quantity

4

4

8

8

Operation Method

Direct-on-line

Volume Control

%

0~100%

Refrigeration Ton

RT

21.9

24.88

33.76

39.52

Refrigerant

Type

1st

R-22

2nd

R-410A

Control Method

Thermostatic expansion valve

Heat Exchanger at Load-side

Type

Brazed Plate type

Circulation Volume

LPM

74.6

88.73

120.48

140.99

Piping(IN/OUT)

A

40x4EA

50x4EA

Heat Exchanger at Heat source- side

Type

Spiral Tube Type

Piping(IN/OUT)

A

150

Control

Temperature Control

Automatic inlet/outlet temperature control

Operation Control

PCB

Weight

kg

640

770

910

1,050

Operational Condition

Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 70°C; Waste water temp to be 25°C

■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.