* Product Overview
A heat pump system that recovers heat from waste water and supplys
the recovered heat to the production of cold/hot water and cooling/heating system
* Features
① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems
* Application
Applicable to any sector that generates waste water and requires hot water such as Sauna, Golf club, Eel farm, Dyeing factory
* Specifications of Waste Water Source Heat Pump (IWB-12BA series)
Model |
IWB-12BA-62 |
IWB-12BA-74 |
IWB-12BA-100 |
IWB-12BA-117 |
||
Capacity |
KW |
218.6 |
260 |
353.02 |
413.14 |
|
Kcal/h |
188,000 |
223,600 |
303,600 |
355,300 |
||
USRT |
62.17 |
73.94 |
100.4 |
117.49 |
||
Power Consumption |
KW |
56 |
66 |
88 |
104 |
|
Power Supply |
3P * 380V * 60Hz |
|||||
Compressor Capacity |
HP |
64 |
72 |
96 |
112 |
|
Dimension |
Length |
mm |
1,700 |
|||
Height |
1,940 |
|||||
Depth |
1,000 |
|||||
Compressor |
Type |
Scroll type |
||||
Quantity |
4 |
4 |
8 |
8 |
||
Operation Method |
Direct-on-line |
|||||
Volume Control |
% |
0~100% |
||||
Refrigeration Ton |
RT |
21.9 |
24.88 |
33.76 |
39.52 |
|
Refrigerant |
Type |
1st |
R-22 |
|||
2nd |
R-410A |
|||||
Control Method |
Thermostatic expansion valve |
|||||
Heat Exchanger at Load-side |
Type |
Brazed Plate type |
||||
Circulation Volume |
LPM |
74.6 |
88.73 |
120.48 |
140.99 |
|
Piping(IN/OUT) |
A |
40x4EA |
50x4EA |
|||
Heat Exchanger at Heat source- side |
Type |
Spiral Tube Type |
||||
Piping(IN/OUT) |
A |
150 |
||||
Control |
Temperature Control |
Automatic inlet/outlet temperature control |
||||
Operation Control |
PCB |
|||||
Weight |
kg |
640 |
770 |
910 |
1,050 |
|
Operational Condition |
Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 70°C; Waste water temp to be 25°C |
■ The above specification may vary depending on the site and temperature conditions.
■ The above specification may change without prior notice for further improvement.