LOGO

IL-JIN E-PLUS

Energy saving device manufacturer, Waste water heat heat pump, Air heat heat pump, Geothermal heat pump and more
Name

Waste Water Source Heat Pump

Model IWH-12A Series
Series Products
Product Description

* Product Overview

A heat pump system that recovers heat from waste water and supplys the recovered heat to the production of cold/hot water and cooling/heating system

 

* Features

① Production of hot or cold water using waste water discharged from public bath or factory, without any environmental contamination the energy saving system promoted by the nation.
② Much economical than oil or city gas (by 70-50%)
③ Safe system free of risk of explosion that exists with oil and gas
④ Excellent economical system as it utilizes waste heat
⑤ Shorter the term of return on investment compared to other systems

 

* Application

Applicable to any sector that generates waste water and requires
hot water such as Sauna, Golf club, Eel farm, Dyeing factory

 

* Specifications of Waste Water Source Heat Pump (IWH-12A series)

Model

IWH-12A-31

IWH-12AB-35

IWH-12A-48

IWH-12A-55

Capacity

KW

108.41

124.57

169.3

194.53

Kcal/h

93,230

107,130

145,600

167,300

USRT

30.83

35.43

48.15

55.32

Power Consumption

KW

32

38

50

58

Power Supply

3P * 380V * 60Hz

Compressor Capacity

HP

30

36

48

56

Dimension

Length

mm

1,200

Height

1,940

Depth

760

Compressor

Type

Scroll type

Quantity

2

4

Operation Method

Direct-on-line

Volume Control

%

0~100%

Refrigeration Ton

RT

11.2

12.52

17.28

19.84

Refrigerant

Type

R-410A

Control Method

Thermostatic expansion valve

Heat Exchanger at Load-side

Type

Brazed Plate type

Circulation Volume

LPM

37

42.51

57.78

66.39

Piping(IN/OUT)

A

40

50

Heat Exchanger

at Heat source- side

Type

Spiral Tube Type

Piping(IN/OUT)

A

125

Control

Temperature Control

Automatic inlet/outlet temperature control

Operation Control

PCB

Weight

kg

410

510

560

590

Operational Condition

Supply side (entry) temp to be 28°C; discharge side (exit) temp to be 70°C; Waste water temp to be 25°C

■ The above specification may vary depending on the site and temperature conditions.